SD Electronic Steam Humidifiers Installation& MaintenanceManualRead and Savethese Instructions
Installation & Maintenance Manual 10 5. Connect Control Wiring 5.1. Controls Placement A typical humidifier control system includes a wall or
SD Carel USA 11 Wiring the CDP Proportional Controller The CDP controller is designed to accept various modulating input signals: 0-10 Vdc, 0-20 V
Installation & Maintenance Manual 12 6. Install Steam Distributor Pipes If your SD 2000 humidifier was supplied with duct steam distributor pip
SD Carel USA 13 7. Install Steam Hoses NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM PIPING FROM THE HUMIDIFIER UNIT
Installation & Maintenance Manual 14 8. Install Room Distribution Unit Models SD101-313: If your SD 2000 humidifier was supplied with a direct
SD Carel USA 15 Models SD323-3B3: The VRDXL used on the SD323-3B3 units is only available as a remote unit (wall mounting bracket supplied), al
Installation & Maintenance Manual 16 9. Start up and Check out of the SD 2000 Humidifier Startup Checklist: 1. Water and drain lines ar
SD Carel USA 17 10. Operating The SD 2000 Humidifier Controller The SD 2000 controllers all have the same general display and keypad as shown belo
Installation & Maintenance Manual 18 CDP 303: control is modulating. The controller has an input for an external modulating signal from a propo
SD Carel USA 19 10.2. Display Sequence Starting Display Appears for 2 seconds on startup. 1. Mod 2. Humidifier model number 3. Controller type (cdC
Installation & Maintenance Manual 2 How The SD 2000 Works The SD 2000 humidifier is what is called an “electrode” humidifier. This means that
Installation & Maintenance Manual 20 Drain Selection Press to change parameter: Cd = drain with electrodes under power td = drain without pow
SD Carel USA 21 11. Maintaining Your SD 2000 Humidifier Although your SD 2000 humidifier is designed to take care of its normal operation, and eve
Installation & Maintenance Manual 22 To clean the fill and drain valves: After shutdown and removal of the steam cylinder, shut off the water
SD Carel USA 23 11.1. Optimizing Cylinder Life on the SD 2000 Electrode Steam Humidifier The normal life of a steam cylinder ranges anywhere from
Installation & Maintenance Manual 24 12. Trouble Shooting The SD 2000 electronic controller contains the most advanced diagnostics available on
SD Carel USA 25 E06 CURRENT TOO HIGH: When amperage exceeds the second safety threshold. Causes: 1. Mineral bridge between electrodes. 2. Leaka
Installation & Maintenance Manual 26 E11 HIGH HUMIDITY: (In CDD models only) Causes: 1. Humidity has exceeded the high limit alarm setpoint.
SD Carel USA 27 WATER IN THE CYLINDER TURNS BLACK: Causes: 1. This is usually an indication that the minerals in the cylinder have overconcentrated
Installation & Maintenance Manual 28 HUMIDIFIER CONTINUOUSLY FILLS AND DRAINS WITHOUT PRODUCING STEAM: Causes: 1. Mineral has bridged between
SD Carel USA 29 POWER CONTACTOR CHATTERS: Causes: 1. Installation dirt has gotten into the contactor and is interfering with its free movement.
SD Carel USA 3 Table of Contents 1. General Installation Rules...
Installation & Maintenance Manual 30 13. Replacement Parts
SD Carel USA 31 Part Number Description Drawing Reference Replacement Steam Cylinders: F201MA0000 1 phase, (SD/OEM-101,102,103) 6 E201MA0000 1
Installation & Maintenance Manual 32 Part Number Description Drawing Reference 1413107AXX Bottom Drain Pan (SD101,102,103,303,305,308,313) 1
SD Carel USA 33
Installation & Maintenance Manual 34
SD Carel USA 35
Installation & Maintenance Manual 36
SD Carel USA 37
Installation & Maintenance Manual 38 14. Technical Specifications UNIT MODEL NUMBER: CAPACITY, AMPERAGE, WATTAGE V Ph. FACTOR 101 102 103 106
SD Carel USA 39 14.1. ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors Model Description Humidity (0-1 VDC or 4-20 mADC) ASWH100
Installation & Maintenance Manual 4 Your SD 2000 steam humidifier will consist of: Steam humidifier unit Steam distributor pipe(s) or Ro
Installation & Maintenance Manual 40 14.2. HC-101 and HC-201 Wall and Duct Humidistats Mounting the HC-101 room humidistat: Mount the HC-101
SD Carel USA 41 14.3. PC-301 Air Proving Switch Mounting the PC-301 air flow switch: Mount the airflow switch in the supply or return duct using
Installation & Maintenance Manual 42 14.4. Condensate Pumps CAREL USAFILENAME: CP-SA-SD CONDENSATE INSTALL-00Created By: BGKDate: 08/30/01Tit
SD Carel USA 43 NOTES:
Installation & Maintenance Manual 44 Form: +03U400125 Rev. 0.0
SD Carel USA 5 1. General Installation Rules Mount the humidifier unit as close to the steam distributor pipe or Remote Distribution Unit as possib
Installation & Maintenance Manual 6 2. Mount Steam Humidifier Sizes and Weights UNIT MODEL NUMBER: DIMENSIONS AND WEIGHT
SD Carel USA 7 2.1. Position of Steam Outlets UNIT MODEL NUMBER: DIMENSIONS DIMENSION 101 102 103 106 303 305 308 313 323 3
Installation & Maintenance Manual 8 3. Connect Plumbing 3.1. Connect Water Feed The water feed connection is a 3/4” MPS male connection on the
SD Carel USA 9 4. Connect Power Wiring Before connecting any power supply, check the data label inside the electrical compartment door to make sure